Governor Model: HYGOV2 and HYGOV2D
Following checks and corrections are applied during Validation and AutoCorrection.
- If 0.0 < T3 < Mult*TimeStep then T3= Mult*TimeStep
- If 0.0 < T4 < Mult*TimeStep then T4= Mult*TimeStep
- If 0.0 < T6 < Mult*TimeStep then T6= Mult*TimeStep
- If 0.0 < Tr < Mult*TimeStep then Tr= Mult*TimeStep
- If Vgmax < 0 then change the sign to positive.
- If Gmax < Gmin then swap the values.
Mult represents the user-specified value Minimum time constant size as multiple of time step option on the Validation page of the Transient Stability Dialog
TimeStep represents the integration time step being used as described on TimeStep
Following treatment is handled during the transient numerical simulation
- If Gate > Pmax , then Pmax = Gate or if Gate < Pmin , then Pmin = Gate
Model Equations and/or Block Diagrams
Parameters for HYGOV2:
| Kp | Proportional gain, pu |
| Ki | Integral gain, pu |
| Ka | Governor gain |
| T1 | Governor mechanism time constant, sec |
| T2 | Turbine power time constant, sec |
| T3 | Turbine exhaust temperature time constant, sec |
| T4 | Governor lead time constant, sec |
| T5 | Governor lag time constant, sec |
| T6 | T, sec |
| Tr | Washout time constant, sec |
| Rtemp | Temporary droop, pu |
| R | Permanent droop, pu |
| Vgmax | Model Parameters\Vgmax |
| Gmax | Maximum gate velocity, pu of mwcap |
| Gmin | Minimum gate velocity, pu of mwcap |
| Pmax | Maximum gate opening, pu of mwcap |
Parameters for HYGOV2D:
| Kp | Proportional gain, pu |
| Ki | Integral gain, pu |
| Ka | Governor gain |
| T1 | Governor mechanism time constant, sec |
| T2 | Turbine power time constant, sec |
| T3 | Turbine exhaust temperature time constant, sec |
| T4 | Governor lead time constant, sec |
| T5 | Governor lag time constant, sec |
| T6 | T, sec |
| Tr | Washout time constant, sec |
| Rtemp | Temporary droop, pu |
| R | Permanent droop, pu |
| Vgmax | Model Parameters\Vgmax |
| Gmax | Maximum gate velocity, pu of mwcap |
| Gmin | Minimum gate velocity, pu of mwcap |
| Pmax | Maximum gate opening, pu of mwcap |
| dbH | Deadband High (pu) |
| dbL | Deadband Low (pu) |
| Trate | Turbine rating, MW |